POWER QUALITY ANALYZER PQ3100

POWER QUALITY ANALYZER PQ3100

POWER QUALITY ANALYZER PQ3100

3-Phase 4-Wire Power Quality Analyzer Compliant to IEC61000-4-30 Class S Standards and On-screen Guide to Deliver Easy Setup and Testing

DESCRIPTION

Hioki portable power meters and analyzers are best in class power measuring instruments for measuring single to three-phase lines with a high degree of precision and accuracy. The PQ3100 is a comprehensive but easy-to-use power quality analyzer for monitoring and recording power supply anomalies, allowing their causes to be quickly investigated, and also for assessing power supply problems such as voltage drops, flicker, harmonics, and other electrical issues.

Key Features
•Record data including voltage, current, power, harmonics, and flicker simultaneously along a single time axis
•Measure up to 6000 A AC
•Capture all power anomalies, including instantaneous outages, voltage drops, and frequency fluctuations, while simultaneously recording trend data
•Quick Set: Easy-to-understand on-screen guide for measurement procedures
•Bundled PQ ONE application software makes it easy to create reports
•Record waveforms for up to 1 second before and 10 seconds after an anomaly occurs
•Accurately measure DC currents over extended periods of time (with an AC/DC auto-zero current sensor)
•Directly supply power to connected current sensors
•Send measured values to HIOKI data loggers using a Bluetooth® wireless technology compatible adapter (LR8410 Link-compatible products), Ver. 2.0 and later

MODEL NO. (ORDER CODE)

PQ3100main unit, clamp sensor is sold separately
PQ3100-02/600 KITkit includes 600 A sensor × 2 and other options
PQ3100-04/600 KITkit includes 600 A sensor × 4 and other options
PQ3100-04/6000-7in KITkit includes 6000 A sensor × 4 and other options

Note: An optional current sensor is necessary to measure current or power parameters. Select from Value Kits for added savings.

LAN
USB 2.0
CE
TrueRMS
RS232C
SD
3 year
sdhc
https://youtube.com/watch?v=_07R76Egzvw%3Frel%3D0%26enablejsapi%3D1%26wmode%3Dopaque

HOW TO USE POWER QUALITY ANALYZERS: RECORDING THE POWER QUALITY OF A POWER GRID

The Hioki PQ3100 Power Quality Analyzer measures all power parameters including voltage, current, power, harmonics, and flicker simultaneously along the same time axis, giving it the ability to capture all power anomalies such as intermittent power interruptions, voltage drops and frequency fluctuations while recording the power trend.

https://youtube.com/watch?v=C-Ik6PTSQ-o%3Frel%3D0%26enablejsapi%3D1%26wmode%3Dopaque

HOW TO USE THE HIOKI PQ3100 POWER QUALITY ANALYZER: A SIMPLE SOLUTION TO WIRING AND CONFIGURATION

The Hioki PQ3100 Power Quality Analyzer provides an intuitive QUICK SET navigation system to simplify the wiring and configuration procedures for measuring a 3-phase system. Connection mistakes such as reversing the direction of the clamp sensor or phase order are automatically detected along with suggestions on how to correct the setup.

https://youtube.com/watch?v=dYOkrdJhi0A%3Frel%3D0%26enablejsapi%3D1%26wmode%3Dopaque

HOW TO USE THE HIOKI PQ3100 POWER QUALITY ANALYZER: MANAGE POWER QUALITY WITH GREATER CONVENIENCE WITH THE PQ ONE BUNDLED APPLICATION

The free PQ ONE application software for the PQ3100 Power Quality Analyzer lets you analyze captured data in fine detail and create regular power quality management reports with ease and flexibility. Investigate the cause of power anomalies in the comfort of your office using your PC.

GET RESULTS FROM THE JOB SITE IN REAL-TIME, GENNECT CROSS SF4000

Capture data on the PC while testing remotely

Learn more

VALUE KITS MODEL: POWER QUALITY ANALYZER KIT PQ3100-91

Model No. (Order Code) PQ3100-91 Kit contents: AC Current sensor CT7136 (600 A) ×2, PQ3100 main unit, SD Memory card 2GB Z4001, Carrying case C1009 Note: Select from Value Kits for added savings.

VALUE KITS MODEL: POWER QUALITY ANALYZER KIT PQ3100-92

Model No. (Order Code) PQ3100-92 Kit contents: AC Current sensor CT7136 (600 A) ×4, PQ3100 main unit, SD Memory card 2GB Z4001, Carrying case C1009 Note: Select from Value Kits for added savings.

VALUE KITS MODEL: POWER QUALITY ANALYZER KIT PQ3100-94

Model No. (Order Code) PQ3100-94 Kit contents: AC Flexible current sensor CT7045 (6000 A) ×4, PQ3100 main unit, SD Memory card 2GB Z4001, Carrying case C1009 Note: Select from Value Kits for added savings.

BASIC SPECIFICATIONS (ACCURACY GUARANTEED FOR 1 YEAR, POST-ADJUSTMENT ACCURACY GUARANTEED FOR 1 YEAR)

Measurement line typeSingle-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement)
Voltage rangesVoltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak
Current ranges50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use)
Power ranges50.000 W to 6.0000 MW (determined automatically based on current range in use)
Basic accuracyVoltage: ±0.2% of nominal voltage, Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy, Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy, AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Measurement items1. Transient over voltage : 200 kHz sampling
2. Frequency cycle : Calculated as one cycle
3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle
4. Voltage swell, Voltage dips, Voltage interruption, RVC(Available in future firmware update) : Voltage (1/2) RMS calculation
5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.
6. Frequency 200 ms: Calculated as 10 or 12 cycles
7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period
8. Voltage waveform peak, Current waveform peak
9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor
10. Voltage crest factor, Current crest factor
11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders
12. Harmonic voltage-current phase angle: 1 th to 50 th orders
13. Total harmonic distortion factor (voltage/ current)
14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders
15. K Factor (multiplication factor)
16. (Available in future firmware update) IEC Flicker, Δ V10 Flicker
RecordMaximum recording interval: 1 year, Maximum number of recordable events: 9999 × 365 days
InterfacesSD/SDHC card, RS-232C (for communication/LR8410 link, available in future firmware update), LAN (HTTP server/FTP/send e-mail, available in future firmware update), USB 2.0 (for communication)
Display6.5-inch TFT color LCD (640 × 480 dots)
Power supplyAC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter)
Dimensions and mass300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack)
AccessoriesInstruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color spiral tube (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1

BASIC SPECIFICATIONS (ACCURACY GUARANTEED FOR 1 YEAR, POST-ADJUSTMENT ACCURACY GUARANTEED FOR 1 YEAR)

Measurement line typeSingle-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel CH4 for voltage/current, (all channels AC/DC measurement)
Voltage rangesVoltage measurement: 1000.0 V rms or DC, Transient measurement 2.200 kV peak
Current ranges50.000 mA AC to 5.0000 kA AC, 10.000 A DC to 2.0000 kA DC
(depends on current sensor in use)
Power ranges50.000 W to 6.0000 MW (determined automatically based on current range in use)
Basic accuracyVoltage: ±0.2% of nominal voltage, Current: ±0.1 % rdg. ±0.1 % f.s. + current sensor accuracy, Active power: DC ±0.5 % rdg. ±0.5 % f.s. + current sensor accuracy, AC ±0.2 % rdg. ±0.1 % f.s. + current sensor accuracy
Measurement items1. Transient over voltage : 200 kHz sampling
2. Frequency cycle : Calculated as one cycle
3. Voltage (1/2) RMS, Current (1/2) RMS: one cycle calculation refreshed every half cycle
4. Voltage swell, Voltage dips, Voltage interruption, RVC(Available in future firmware update) : Voltage (1/2) RMS calculation
5. Inrush current : half-cycle calculation: Calculated as the current RMS value for current waveform data sampled every half-cycle.
6. Frequency 200 ms: Calculated as 10 or 12 cycles
7. 10-sec frequency: Calculated as the whole-cycle time during the specified 10 s period
8. Voltage waveform peak, Current waveform peak
9. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Apparent energy, Reactive energy, Energy cost, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor
10. Voltage crest factor, Current crest factor
11. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0 th to 50 th orders
12. Harmonic voltage-current phase angle: 1 th to 50 th orders
13. Total harmonic distortion factor (voltage/ current)
14. Inter harmonic (voltage/ current): 0.5 th to 49.5 th orders
15. K Factor (multiplication factor)
16. (Available in future firmware update) IEC Flicker, Δ V10 Flicker
RecordMaximum recording interval: 1 year, Maximum number of recordable events: 9999 × 365 days
InterfacesSD/SDHC card, RS-232C (for communication/LR8410 link, available in future firmware update), LAN (HTTP server/FTP/send e-mail, available in future firmware update), USB 2.0 (for communication)
Display6.5-inch TFT color LCD (640 × 480 dots)
Power supplyAC adapter Z1002 (100 V to 240 V AC, 50/60 Hz, rated current 1.7 A), Battery pack Z1003 (Continuous use: 8 hr, Charging time: Max. 5 hr 30 m with AC adapter)
Dimensions and mass300 mm (11.81 in)W × 211 mm (8.31 in)H × 68 mm (2.68 in)D, 2.5 kg (88.2 oz) (including battery pack)
AccessoriesInstruction manual ×1, Measurement guide ×1, Voltage cord L1000-05 ×1 set (Red/Yellow/Blue/Gray/Black, Alligator clip ×5, Spiral tube ×5), Color spiral tube (for identifying clamp sensor color) ×1 set, Spiral tube ×5, AC adapter Z1002 ×1, Strap ×1, USB cable (1 m 3.28 ft length) ×1, Battery pack Z1003 ×1, PQ ONE (software, CD) ×1

OPTIONS

AC/DC current input

AC/DC AUTO-ZERO CURRENT SENSOR CT7742

・ DC to 5 kHz (-3dB) ・ Rated 2000 A AC/DC ・φ 55 mm (2.17 in) core dia.

AC/DC AUTO-ZERO CURRENT SENSOR CT7736

・ DC to 5 kHz (-3dB) ・ Rated 600 A AC/DC ・φ 33 mm (1.30 in) core dia

AC/DC AUTO-ZERO CURRENT SENSOR CT7731

・ DC to 5 kHz (-3dB) ・ Rated 100 A AC/DC ・ φ 33 mm (1.30 in) core dia.

Cases

Waterproof Box
For outdoor installation; IP65 compliant, Contact Hioki for a quotation.

CARRYING CASE C1009

Bag type, Includes compartment for options

CARRYING CASE C1002

For the PW3198, hard trunk type, for storing options

CARRYING CASE C1001

Soft type, Includes compartment for options

Current input

For power or load current measurement (1 sensor necessary for single-phase measurements, and 2 or 3 sensors required for 3-phase measurements)

AC FLEXIBLE CURRENT SENSOR CT7040 series

• 10 Hz to 50 kHz (±3dB) • 600A or 6000A AC rated • φ 254 mm (10.00 in) loop dia. to φ 100 mm (3.94 in)

AC CURRENT SENSOR CT7136

600 A AC, φ46 mm (1.81 in), 2.5 m (8.20 ft) cord length

AC CURRENT SENSOR CT7131

100 A AC, φ15 mm (0.59 in), 2.5 m (8.20 ft) cord length

AC CURRENT SENSOR CT7126

60 A AC, φ15 mm (0.59 in), 2.5 m (8.20 ft) cord length

Current Input 2000A AC/DC

* The CT9920 is necessary for connecting the current sensor with HIOKI PL14 to the PW3390

AC/DC AUTO-ZERO CURRENT SENSOR CT7742

・ DC to 5 kHz (-3dB) ・ Rated 2000 A AC/DC ・φ 55 mm (2.17 in) core dia.

Current Input 6000A

* The CT9920 is necessary for connecting the current sensor with HIOKI PL14 to the PW3390

AC FLEXIBLE CURRENT SENSOR CT7040 series

• 10 Hz to 50 kHz (±3dB) • 600A or 6000A AC rated • φ 254 mm (10.00 in) loop dia. to φ 100 mm (3.94 in), 3 loop diameters

Interface Cables

LAN CABLE 9642

Straight Ethernet cable, supplied with straight to cross conversion adapter, 5 m (16.41 ft) length

Leak current input

*For leak current measurement (not capable of power measurement)

AC LEAKAGE CURRENT SENSOR CT7116

6 A AC, φ40 mm (1.57 in), 2.5 m (8.20 ft) cord length

Options

MAGNETIC ADAPTER 9804-02

Attaches to the tip of cord, black ×1, φ11 mm (0.43 in)

Options for Differential Probes

Can also be used with accessories such as L4936/L4937/L4931 as available for other testers.

GRABBER CLIP 9243

Attaches to the tip of the banana plug cable, Red/ Black: 1 each, 196 mm (7.72 in) length, CAT III 1000 V

Other options

*C0203 is bundled.

CONVERSION CABLE L9910

Used to connect the current sensors with BNC terminal to PL14 terminal (example the PQ3100)

PC communication

*The 9151-02 is only for the RM3545-01

RS-232C CABLE 9637

For the PC, 9 pin – 9 pin, cross, 1.8 m (5.91 ft) length

PC peripherals

GENNECT CROSS SF4000

• Software automatically recognizes LAN-connected measuring instrument • Display acquired data as graphs in real-time • Windows compatible

Power supply

*AC adapter is bundled with the LR8410-20, LR8510/8511, LR8450, LR8450-01

BATTERY PACK Z1003

NiMH, Charges while installed in the main unit

AC ADAPTER Z1002

For main unit, 100 to 240 V AC

Storage media

Precaution on purchasing memory device


Use only the memory device sold by HIOKI. Compatibility and performance are not guaranteed for memory device made by other manufacturers. You may be unable to read from or save data to such devices.

SD MEMORY CARD Z4003

8 GB capacity

SD MEMORY CARD 2GB Z4001

2 GB capacity

Strap options

When using with the PQ 3100, suspend the main body on the metal surface using two Z5020 powerful type. Z5004 hang the cords on the metal surface.

MAGNETIC STRAP Z5020

Extra strength

MAGNETIC STRAP Z5004

Voltage Input

*The L1000 is bundled with PQ3198 *Please inquire about voltage cord extension

MAGNETIC ADAPTER 9804-01

Attaches to the tip of cord, red ×1, φ11 mm (0.43 in)

VOLTAGE CORD L1000-05

Red/ Yellow/ Blue/ Gray/Black each 1, 3 m (9.84 ft) length

GRABBER CLIP 9243

Attaches to the tip of the banana plug cable, Red/ Black: 1 each, 196 mm (7.72 in) length, CAT III 1000 V

MAGNETIC ADAPTER 9804-02

Attaches to the tip of cord, black ×1, φ11 mm (0.43 in)

Voltage measurement

*PW9020 ×4 pieces are bundled, additional single sensors also available

MAGNETIC ADAPTER 9804-01

Attaches to the tip of cord, red ×1, φ11 mm (0.43 in)

Categories